Parameters list
Important
The ability to manage over a local network without a security token is blocked by default for security reasons. This may be relevant, for example, when using local control in public places. If this security measure is not needed, disable it on the device by setting the bLc parameter to oFF. Otherwise, requests for changes without this token will not be executed.
To retrieve the set of all available parameters for a specific device, send the request {“cmd”:1}. The response for an OZ thermostat without an air sensor, manufactured before June 2025, is:
{
"sn":"404CCAAAD4E8A89860609800000149",
"par":[[0,6,"536112000"],[1,6,"536112000"],
[2,2,"1"],[3,2,"0"],[5,1,"30"],
[7,1,"5"],[17,4,"175"],[18,2,"2"],
[19,2,"10"],[21,1,"0"],[23,2,"6"],
[25,2,"15"],[26,1,"45"],[27,1,"5"],
[28,2,"16"],[29,1,"0"],[31,1,"8"],
[52,4,"0"],[53,4,"480"],[55,2,"24"],
[80,1,"0"],[81,1,"0"],[82,1,"0"],
[109,7,"0"],[114,7,"1"],[115,7,"0"],
[117,7,"0"],[118,7,"0"],[120,7,"0"],
[121,7,"0"],[124,7,"0"],[125,7,"0"]]
}
sn - device serial number
par - parameter exchange key
Transfer format is an array of arrays. The first value is number of the parameter, the second its type, the third is string with the parameter value.
For example, turn on the device and set floor temperature in manual mode to 27 °C (device menu item bLc = 0FF, blocking is disabled):
{
"sn":"404CCAAAD4E8A89860609800000149",
"par":[[125,7,"0"],[5,1,"27"]]
}
Answer:
In response, we receive an updated list of parameters:
{
"sn":"404CCAAAD4E8A89860609800000149",
"par":[[0,6,"536112000"],[1,6,"536112000"],
[2,2,"1"],[3,2,"0"],[5,1,"27"],
[7,1,"5"],[17,4,"175"],[18,2,"2"],
[19,2,"10"],[21,1,"0"],[23,2,"6"],
[25,2,"15"],[26,1,"45"],[27,1,"5"],
[28,2,"16"],[29,1,"0"],[31,1,"8"],
[52,4,"0"],[53,4,"480"],[55,2,"24"],
[80,1,"0"],[81,1,"0"],[82,1,"0"],
[109,7,"0"],[114,7,"1"],[115,7,"0"],
[117,7,"0"],[118,7,"0"],[120,7,"0"],
[121,7,"0"],[124,7,"0"],[125,7,"0"]]
}
Note
The floor sensor temperature in the user menu and via API can be changed in 1 °C increments over the entire operating range.
Important
When changing device parameters, the command must contain the key sn
Num |
Type |
|---|---|
0 |
CStringType |
1 |
int8 |
2 |
uint8 |
3 |
int16 |
4 |
uint16 |
5 |
int32 |
6 |
uint32 |
7 |
bool |
Num |
Type |
Name |
Description |
|---|---|---|---|
0 |
6(uint32) |
startAwayTime |
in seconds from 01.01.2000, away start time |
1 |
6(uint32) |
endAwayTime |
in seconds from 01.01.2000, away end time |
2 |
2(uint8) |
mode |
mode: schedule=0, manual=3 |
3 |
2(uint8) |
controlType |
control tupe: by floor=0 |
5 |
1(int8) |
manualFloorTemperature |
in °C, manual mode temperature by floor |
6 |
1(int8) |
awayAirTemperature |
in °C, temperature mode away by air |
7 |
1(int8) |
awayFloorTemperature |
in °C, temperature mode away by floor |
17 |
4(uint16) |
power |
in a.e., If the «Р» is less than or equal to 150, then P = power * 10. If the «Р» is greater than 150, then P = power * 20 - 1500. As a result, we get the specified connected power in Watts. |
18 |
2(uint8) |
sensorType |
type of connected temperature sensor: 4,7kOhm=0, 6,8kOhm=1, 10kOhm=2, 12kOhm=3, 15kOhm=4, 33kOhm=5, 47kOhm=6 |
19 |
2(uint8) |
histeresis |
in °C*10, hysteresis |
21 |
1(int8) |
floorCorrection |
in °C*10, floor temperature sensor correction |
23 |
2(uint8) |
brightness |
in a.e. (from 0 to 9) brightness |
25 |
2(uint8) |
propKoef |
in minutes when load on within 30-minutes cycle of the proportional mode |
26 |
1(int8) |
upperLimit |
in °C, max setting value of the floor temperature |
27 |
1(int8) |
lowerLimit |
in °C, min setting value of the floor temperature |
28 |
2(uint8) |
maxSchedulePeriod |
max number of perioods per day. Read Only |
29 |
1(int8) |
tempTemperature |
in °C, temporary mode temperature |
31 |
1(int8) |
setTemperature |
in °C, setting temperature of current mode (awayFloorTemperature | manualFloorTemperature | tempTemperature) |
52 |
4(uint16) |
nightBrightStart |
in minutes from 00:00, night low bright start time |
53 |
4(uint16) |
nightBrightEnd |
in minutes from 00:00, night low bright end time |
55 |
2(uint8) |
relayOnTimeLimit |
in hours, continuous heating time for emergency alert (Read-only) |
80 |
1(int8) |
buttonMinusCor |
Correction of sensitivity of key sensors from -30 to 30 |
81 |
1(int8) |
buttonMenuCor |
Correction of sensitivity of key sensors from -30 to 30 |
82 |
1(int8) |
buttonPlusCor |
Correction of sensitivity of key sensors from -30 to 30 |
109 |
7(bool) |
offButtonLock |
disable automatic lock of touch buttons (Read-only) |
114 |
7(bool) |
lanBlock |
local newort control block: 0 - disabled, 1 - enabled |
115 |
7(bool) |
cloudBlock |
cloud control block: 0 - disabled, 1 - enabled |
117 |
7(bool) |
NCContactControl |
inverted relay: 0 - disabled, 1 - enabled |
118 |
7(bool) |
coolingControlWay |
mode: 0 - heating, 1 - cooling |
120 |
7(bool) |
useNightBright |
activate using night bright: 0 - disabled, 1 - enabled |
121 |
7(bool) |
preControl |
preheat: 0 - disabled, 1 - enabled |
124 |
7(bool) |
childrenLock |
children protect: 0 - disabled, 1 - enabled |
125 |
7(bool) |
powerOff |
power off: 0 - enabled, 1 - disabled |
Note
Setpoints for all modes must fit within limits for parameters 26 and 27